VERSAMETER™ FLOW METER - Nitrex
Search
Close this search box.
Search
Close this search box.

- VERSAMETER™ FLOW METER -

chevron-right
chevron-right
VERSAMETER™ FLOW METER

VERSAMETER™ FLOW METER

DIFFERENTIAL PRESSURE METER FOR PRECISE & RELIABLE CONTROL OF ATMOSPHERE GASES & LIQUIDS

 

The VersaMeter™ represents a full range of precision flow measurement instruments utilizing our certifiable differential pressure flow measurement design, proven to meet the rugged requirements of industrial heat-treatment applications. The advanced touchscreen-based calibration and display modules include integrated flow rate alarm and flow consumption totalizing functions.

The VersaMeter™ is designed to fit direction into a pipeline assembly and can provide either local or remote display options. The VersaMeter™ meets current NFPA86 guidelines for safe usage in the thermal processing industry. In addition, every VersaMeter™ comes complete with a 10point calibration curve traceable to a NIST transfer standard. The meters can also be field calibrated to meet CQI-9, ISO, NADCAP and QS quality audit systems.

The VersaMeter™ product line comes in many sizes and is designed to fit directly into equipment piping. The VersaMeter valve assemblies fit standard pipe fittings to better integrate into your equipment design while making it easier to access and maintain pipeline components.

Documents

FEATURES & BENEFITS

  • Meets NFPA requirements
  • Infield calibration verification
  • No moving parts
  • Integrated touchscreen display
  • Remote display option
  • Integrated Flow Alarm
  • Integrated Flow Totalizer
  • Multipoint calibration

SYSTEM CHARACTERISTICS

Power requirements:No power required
Ambient Temperature: 32°-150°F
Max Inlet Pressure 2 PSI (Standard Model)
40 PSI (HP Model)
250 PSI (HPX Model)
Flow Accuracy: ± 4%
Repeatability: 2%
Flow Output Signal (linear): 4-20MA or RS-485
Flow Control Signal (linear): 4-20MA or RS-485
Flow Output Signal: SPDT Relay
Turndown: 15-100%

CHARACTERISTICSSTANDARD OPTIONHP OPTION
Scale:To OrderTo Order
Turndown:10:110:1
Accuracy:+/- 4%+/- 4%
Max Pressure:5 psig80 psig
Max Temperature:130°F130°F
Power:24VDC24VDC
Flow Signal:4-20mA4-20mA
Control Signal:4-20mA4-20mA
Flow Switch:YesYes
Comms Serial:RS-485RS-485
Protocol:ModBUS-RTUModBUS-RTU
Ethernet Port:TCP/IPTCP/IP

Still Have questions?

Can’t find what you’re looking for? Please feel free to get in touch with our experts.