FURNACEMETER™ FLOW METER - Nitrex

- FURNACEMETER™ FLOW METER -

FURNACEMETER™ FLOW METER

FURNACEMETER™ FLOW METER

DIFFERENTIAL PRESSURE FLOW METER

 

The FurnaceMeter™ represents a full range of precision flow measurement instruments utilizing our proprietary differential pressure flow measurement design proven to meet the rugged requirements of industrial heat-treatment applications. The meters utilize precision, field-proven, and certifiable differential pressure flow measurement sensors. The advanced calibration and display modules on the electronic versions include integrated flow rate alarm and flow consumption totalizing functions.The FurnaceMeter™ meets current NFPA86 guidelines for safe usage in the thermal processing industry. In addition, every FurnaceMeter™ comes complete with a 10point calibration curve traceable to a NIST transfer standard. The meters can also be field calibrated to meet CQI-9, ISO, NADCAP and QS quality audit systems.

The FurnaceMeter™ is available for either gas or liquid flow measurement. These meters can also be fitted with integrated manual flow control valves specifically designed for the gas type, inlet pressures, and scale ranges to provide precision process control for most applications.

The FurnaceMeter™ provides a retrofit footprint to most variable area meters to minimize piping changed when upgrading to differential pressure technology and in-situ calibration capabilities.

Documents

CARACTÉRISTIQUES ET AVANTAGES

  • Répond aux exigences de la NFPA
  • Vérification de l’étalonnage du champ intérieur
  • Vanne de contrôle de précision intégrée et motorisée
  • Aucune pièce mobile pour la mesure du débit
  • Écran tactile intégré
  • Option d’affichage à distance
  • Alarme de débit intégrée
  • Totalisateur de débit intégré
  • Étalonnage multipoint

CARACTÉRISTIQUES DU SYSTÈME

Power requirements:No power required
Ambient Temperature: 32°-150°F
Max Inlet Pressure 2 PSI (Standard Model)
40 PSI (HP Model)
250 PSI (HPX Model)
Flow Accuracy: ± 4%
Repeatability: 2%
Flow Output Signal (linear): 4-20MA or RS-485
Flow Control Signal (linear): 4-20MA or RS-485
Flow Output Signal: SPDT Relay
Turndown: 15-100%

*Calibration is referenced to standard atmospheric conditions: (70°F, 14.7 PSIA)

CARACTÉRISTIQUESOPTION STANDARDOption HP
Échelle :À commanderÀ commander
Variation de débit 10:110:1
Précision :+/- 4%+/- 4%
Pression maximale :5 psig80 psig
Température maximale :130°F130°F
Puissance :24VDC24VDC
Signal de débit :4-20mA4-20mA
Signal de contrôle :4-20mA4-20mA
Fluxostat :YesYes
Transmission série :RS-485RS-485
Protocole :ModBUS-RTUModBUS-RTU
Port Ethernet :TCP/IPTCP/IP

TÉLÉCHARGEMENTS

Still Have questions?